Keypad panel display
Alarm Name
Contents of operation
During
acceleration
If the inverter output current momentarily exceeds the overcurrent
detection level due to an overcurrent in the motor, or a short-circuit
or a ground fault in the output circuit, the protective function is
activated.
During
deceleration
Running at
constant speed
If a ground fault in the inverter output circuit is detected, the protective function is
activated (for 40HP or more only). If a ground fault occurs in an inverter rated at
30HP or less, the inverter is protected by the overcurrent protection. If protection
against personal injury or property damage is required, install a ground-fault
protective relay or earth-leakage circuit breaker separately.
During
acceleration
If the DC link circuit voltage of the main circuit exceeds the
overvoltage detection level (230V series: 400V DC,460V series:
800V DC) due to an increase in the regenerating current from the
motor, the output is shut down.
However, protection against inadvertent overvoltage apply (e.g.,
high-voltage line) may not be provided.
During
deceleration
Running at
constant speed
If the DC link circuit voltage of the main circuit falls below the undervoltage detection
level (230V series: 200V DC,460V series: 400V DC) due to a lowered power supply,
the output is shut down. If function code F14 (Restart after momentary power failure)
is selected, an alarm is not displayed. In addition, if the supply voltage falls to a
level unable to maintain control power, an alarm may not be displayed.
If the inverter is driven with any one of the three phases connected to L1/R, L2/S and L3/T
of the main circuit power supply “open”, the rectifying diodes or smoothing capacitors may
be damaged, at such time an alarm is issued and the inverter is tripped.
Overheating of heat
sink
If the temperature of the heat sink rises due to a cooling fan failure, etc., the
protective function is activated.
If the external alarm contacts of the braking unit, braking resistor or external thermal
O/L relay are connected to the control circuit terminals (THR), this alarm will be
actuated according to contact off signal.
When the PCT thermal protection is activated(H26:1), it operates when the detected
temperature is increased.
Inverter internal
overheating
HIGH AMB TEMP
If the temperature inside the inverter rises due to poor ventilation, etc., the protective
function is activated.
Overcurrent of the terminal 13(20mA or more) due to the short circuit between the
terminal 13 and 11, etc., the protective function is activated.
Overheating of
braking resistor
If electronic thermal O/L relay (for braking resistor) function code F13 is selected, the
protective function is activated to prevent the resistor from burning due to overheating
following frequent use of the braking resistor.
The protective function is activated if the motor current exceeds the preset level,
provided that electronic thermal O/L relay 1 function code F10 has been selected.
If the second motor current exceeds the preset level when the operation is switched
to drive the second motor, the protective function is activated, provided that
electronic thermal O/L relay 2 of function code A04 is selected.
If the output current exceeds the rated overload current, the protective function is
activated to provide thermal protection against semiconductor element overheating in
the inverter main circuit.
If the fuse in the inverter is blown out following a short-circuit or damage to the
internal circuit, the protective function is activated (for 40HP or more only).
If a memory error occurs, such as missing or invalid data, the protective function is
activated.
Keypad panel
communication
error
If a communication error or interrupt between the keypad panel and control circuit is
detected, the protective function is activated.
Er4
Er5
OPTN COM ERR
OPTION ERROR
If there is an open circuit or a connection error in the inverter output wiring during
performing auto-tuning, the protective function is activated.
RS-485
communication error
Source: https://suachuatulanh.org
Category : Thợ Lò Vi Sóng
Có thể bạn quan tâm
- Biến tần nguồn áp và một số phương pháp điều khiển động cơ KĐB (09/08/2023)
- Biến tần FR-A800 Mitsubishi (08/08/2023)
- Đại lý ABB Việt Nam | Đại lý phân phối ABB tại Việt Nam (08/08/2023)
- Biến tần LS SV015IC5-1, 1.5KW, Input 1P (200 ~240VAC) (08/08/2023)
- Lắp đặt biến tần invt cho thủy điện Cửa Đạt ở Thanh Hóa – 2023 (08/08/2023)
- Biến tần INVT 37kW 3 Pha 380V – GD200A-037G/045P-4 (08/08/2023)